Data Center Technical Specs

Facility Specifications

Data center leasable/co-location space consists of 4 separate suites

  • Suite #1: 2098 sq feet
  • Suite #2: 2385 sq feet
  • Suite #3: 2233 sq feet 
  • Suite #4: 2385 sq feet

Floor load: 250 lbs per square foot

Roughly 11 feet between the raised floors and the ceiling

24 inch raised flooring

Ground ring protection against lightning and power surges

Exterior blast proof walls

Electrical Power Systems

Cost

Approximately .09/kWH

Commercial Power

Runs off commercial power, backed up by a standby generator, 120 or 208 volt with two 20 or 30 amp circuits

Battery Backup

A redundant battery backup provides 120 or 208 volt with two 20 or 30 amp circuits

Standby Generator

1,000 Gallon 800 KW Diesel Generator, with a 24 hour run time

Network Connectivity

Multiple active Internet connections

Redundant diverse fiber paths

Additional bandwidth is available with built-in scalability 

Environmental Controls

Fire Suppression

Fire suppression system utilizing Fike’s Ecaro-25

Ecaro-25 features fire-extinguishing agent FE-25 by DuPont. FE-25 absorbs heat energy at its molecular level faster than the heat can be generated, so the fire cannot sustain itself.

FE-25 also forms free radicals to chemically interfere with the chain reaction of the combustion process. This highly effective clean agent is safe for people, assets and the environment. FE-25 is:

  • Zero Ozone Depleting Potential (ODP)
  • Environmentally Safe
  • Electrically Non-Conductive
  • Colorless and Odorless
  • Leaves No Residue
  • No Over pressurization Concerns

HVAC

N+1 Liebert Drycoolers 60 Hz

N+1 Liebert Chillers

N+1 Glycol Pumps

Temperature

65 - 72 degrees F, monitored  to stay within that range 24x7x365

Humidity

35 - 50 %, monitored to stay within that range 24x7x365

Security Systems

Two Factor, key pad and RFID card exterior authentication

Man Trap

Biometric Iris Scanning authentication access to interior data center and data center suites

Locked cages and server cabinets

Exterior and interior video surveillance

Access controlled meet me/electrical room

Access controlled glycol pump house

System Monitoring

On site monitoring systems provide real time information on all critical support systems

Temperature, humidity and power are monitored 24x7x365

Fire and water detectors are also in place and monitored 24x7x365

 